精神科護理站空氣品質改善方案

A Project to Improve Psychiatric Nursing Station Air Quality

摘要


Background: Ambient air at the psychiatric nursing station in our hospital had been notably poor for an extensive period of time. CO2 levels at the station averaged 1211 ppm during August, 2009 and a specialist team estimated a CO2 abnormality ratio of 32%. Analysis identified key issues in three problem areas, including (1) Environment: air at the station was not refreshed and electronic equipment was in constant operation; (2) Staff: the station had a high staff-tospace ratio and staffs lacked practical knowledge on indoor air quality maintenance; and (3) Policy: the hospital had no guidelines addressing indoor air quality maintenance.Purpose: The purpose of this project was to reduce ambient CO2 levels at the hospital’s acute psychiatric ward in order to create a high-quality working environment for all staff. The short-term goal was to reduce the CO2 abnormality ratio from 32% to 10%. Long-term goals were to maintain an ambient CO2 level in the ward below 1000ppm and further reduce the abnormality ratio to 0%.Methods: To address environment-related issues, we increased the number of indoor plants and turned certain computers off at night. To address staff-related issues, we rearranged staff activity space and educated staff on how to maintain indoor air quality. To address the policy-related issue, we drafted proposed hospital guidelines on indoor air quality maintenance.Results: Post-intervention measurements made in October, 2011 found significantly improved ambient air quality, with CO2 levels at 997ppm and a CO2 abnormality ratio of 0%.Conclusions: Results demonstrate that improvement measures implemented can effectively improve the quality of ambient air at psychiatric nursing stations. A post-intervention survey further found that staffs were both more satisfied with ward air quality and perceived a friendlier ward work environment.

並列摘要


Background: Ambient air at the psychiatric nursing station in our hospital had been notably poor for an extensive period of time. CO2 levels at the station averaged 1211 ppm during August, 2009 and a specialist team estimated a CO2 abnormality ratio of 32%. Analysis identified key issues in three problem areas, including (1) Environment: air at the station was not refreshed and electronic equipment was in constant operation; (2) Staff: the station had a high staff-tospace ratio and staffs lacked practical knowledge on indoor air quality maintenance; and (3) Policy: the hospital had no guidelines addressing indoor air quality maintenance.Purpose: The purpose of this project was to reduce ambient CO2 levels at the hospital’s acute psychiatric ward in order to create a high-quality working environment for all staff. The short-term goal was to reduce the CO2 abnormality ratio from 32% to 10%. Long-term goals were to maintain an ambient CO2 level in the ward below 1000ppm and further reduce the abnormality ratio to 0%.Methods: To address environment-related issues, we increased the number of indoor plants and turned certain computers off at night. To address staff-related issues, we rearranged staff activity space and educated staff on how to maintain indoor air quality. To address the policy-related issue, we drafted proposed hospital guidelines on indoor air quality maintenance.Results: Post-intervention measurements made in October, 2011 found significantly improved ambient air quality, with CO2 levels at 997ppm and a CO2 abnormality ratio of 0%.Conclusions: Results demonstrate that improvement measures implemented can effectively improve the quality of ambient air at psychiatric nursing stations. A post-intervention survey further found that staffs were both more satisfied with ward air quality and perceived a friendlier ward work environment.

參考文獻


王建楠、吳重達(2004).病態建築物症候群.中華職業醫 學雜誌,11(4),251- 260。[Wang, J. N., & Wu, C. T. (2004). Sick-building syndrome. Chinese Journal of Occupational Medicine, 11(4), 251- 260.]
李良梧(1993).室內空氣品質與通風.中國冷凍空調雜誌, 6,79- 86。[Li, L. W. (1993). Indoor air quality and ventilation. Zhong Guo Leng Dong Kong Diao Za Zhi, 6, 79- 86.]
郭博文(2009).植栽改善空氣中二氧化碳濃度之研究.環 境與生態學報,2(1),53- 61。[Kuo, P. W. (2009). A research on the carbon dioxide distribution in the indoor environment and uses plants to improve the indoor air quality. Journal of Ecology and Environmental Sciences, 2(1), 53- 61.]
麥富德、蔡佳芳、許又文、陳文貴(2005).醫院室內空 氣品質的監測.科儀新知,27(1),73- 80。[Mai, F. D., Tsai, C. F., Hsu, Y. W., & Chen, W. K. (2005). The detection of hospital indoor air quality. Instruments Today, 27(1), 73- 80.]
黃東海(2007).既有辦公建築室內空氣品質改造及檢測 之研究—以高雄市辦公建築為例(未發表的碩士論 文).台南市:國立成功大學建築研究所。[Huang, T. H. (2007). A study of the improvement and examination on IAQ for office buildings in Kaohsiung (Unpublished master’s thesis). National Cheng Kung University, Tainan City, Taiwan, ROC.]

延伸閱讀