Induced capacitive voltage and current in high voltage GIS substation is one of the most significant phenomena that may have made some problems in this substation operation. At this study the various equipment of 420 KV Karoon4 substations such as powerhouses, input and output lines, bus-bar and bus-duct have simulated by applying EMTP-RV software. Then with the different condition of single-phase and three-phase faults on the lines in critical conditions, capacitive induction voltage and current by parallel capacitor with circuit breaker is surveyed. The results show the value of this induced current and voltage and that this critical conditions the breakers and disconnector switches must be able to interrupt this value of current.