145kV斷路器試驗電路元件值設定

Setting of Element Values of 145kV Circuit Breaker Test Circuit

指導教授 : 陳昭榮
若您是本文的作者,可授權文章由華藝線上圖書館中協助推廣。

摘要


暫態恢復電壓為高壓氣體絕緣開關設備短路試驗之關鍵數據,亦為斷路器啟斷能力評估的重要依據。本論文以Matlab/Simulink軟體及EMTP/ATP電磁暫態分析軟體模擬出四參數電路模型在斷路器啟斷瞬間的暫態恢復電壓波形,以檢驗暫態恢復電壓值是否符合IEC國際標準。本論文使用荷蘭電力試驗機構(KEMA)試驗電路之模型,來分析試驗電路參數和暫態恢復電壓之關係。 斷路器在試驗過程中暫態恢復電壓會因為環境因素而改變,將電壓變動範圍調整到IEC國際標準範圍內為試驗機構重要的技術。本論文利用程式將可變動元件逐一代入電路模型,經過一連串的模擬找出在符合IEC國際標準之下的元件變動量,以期待在實際試驗時能有調整元件的參考依據。

並列摘要


Transient recovery voltage is important data of high-voltage gas insulated switchgear short-circuit test. It’s also assessment breaking capacity quite important basis. In this paper was useful Matlab / Simulink software and EMTP / ATP software to simulate of electromagnetic transient analysis in the four-parameter model of Circuit Breaker Transient Recovery voltage waveforms. To test the value of transient recovery voltage whether match with standards of IEC.Using of the Dutch testing institutions of power (KEMA) on the test circuit model to analyze the test circuit and the relationship between the transient recovery voltage. Transient Recovery Voltage in the braker will be affected by the eniorment.To control the variable voltage value within IEC standard is an very important technique of the testing institution.We use the method of programming to test the variable devices in a circuit model. After a series of testing, author find out the variable value under IEC standard, and hopefully to build a reference to adjust the value and specification of devices in experiments.

參考文獻


[16] 阮栢村,以有限元素法分析GIS斷路器之啟斷特性及開關突波特性,碩士論文,中原大學,桃園,2003。
[1] Gardner,G.E; Unwin,R.J“Development testing techniques for Airblast and SF6 Switchgear”IEE Transmission and distribuition,Vol.127,No 5, September 1980, pp.285-293.
[3] Hanriot,J.M; Guillox,C.Lergos,W.P;Genon,A.M;Belgium,P.G“Digital Acquisition and Numerical Processing of Measuring Signals in a High Voltage Circuit Breaker Testing Laboratory” IEEE Transations on Power Delivery, Vol.1,No.3, July 1986, pp.134-139.
[4] Ren Fu,Wang“Calculation and Adjustment Limitation of Four-Parameter TRV in High Power Testing Circuits and Their Comparison”IEEE Transations on Power Delivery, Vol.2, No.3,July 1987, pp.758-764.
[5] Lou van der Sluis,L;.Rutgers ,W.R“Comparison of Test Circuits for High Voltage Circuit Breakers by Numerical Calculation With Arc Models” IEEE Transations on Power Delivery,Vol.7,No.4, October 1992, pp.2037-2045.

延伸閱讀