  • 學位論文

使用微霧技術對VRF系統節能效果之分析-以辦公室為例

Energy Saving Evaluation of the Application of Misting Technology on VRF Systems – Using An Office Building as An Example

指導教授 : 柯明村

摘要


隨著人們依賴冷氣程度日益升高,家用分離式冷氣日益普及,也開啟商用分離式空調系統的市場。VRF(Variable Refrigerant Flow,變冷媒流量,簡稱VRF)系統為商用直膨變頻分離式冷氣系統的一種,其性能效率受外氣溫度影響很大,本研究希望以實際使用案例分析採用微霧系統對降低室外主機進風溫度及節能的影響,期望以最低的成本達到最佳的節能效果。 本研究結果顯示微霧系統可以降低空調機房進風溫度,最大可降低1.5℃。對VRF系統室外機冷凝器進風溫度,250型主機最大可降低3.8℃,平均可降低1.23℃;800型主機最大可降低4.5℃,平均也可降低1.21℃。在節能效益分析方面,250型主機最大可節能5.29%,總平均節能只有1.15%;在800型主機最大可節能12.33%,總平均節能3.97%。

關鍵字

VRF 節能 COP 微霧

並列摘要


When people deeply rely on air conditioning, residential split air conditioner is getting popular. It also introduces the commercial split air conditioner to the market. VRF (variable refrigerant flow) system is kind of major commercial split air conditioners. Basically, the performance and efficiency of VRF would be influenced by outside air temperature. This study is to analysis the effect of the misting system on reducing the supply air temperature and energy saving consequence. We are attempted to spend the lowest cost but meet the achievement of best energy saving performance. The result shows that the misting system can reduce supply air temperature by 1.5℃ maximum. As per VRF type 250, it also reduces the supply air temperature of condenser by 3.8℃ maximum and averaged by 1.23℃. When evaluating to type 800, it may reduce 4.5℃ maximum with the average of 1.21℃. Compared type 250 to type 800 in the aspect of energy saving, maximum saving ratios are 5.29% and 12.33% respectively; total averaged saving ratios are 1.15% and 3.97% respectively.

並列關鍵字

VRF energy saving COP misting

參考文獻


[13] 曹仲春,「建築大樓陣列式分離式空調室外機散熱問題分析」,國立台北科技大學碩士論文,民96,第53-62頁。
[2] MITSUBISHI ELECTRIC CORRPORATION, “CITY MULTITM DATA BOOK”,Sep.2005.
[8] D. Y. Goseami, G. D. Mathur and S. M. Kulkarni, ”Experimental Investigation of Performance of a Residential Air Conditioning System with an Evaporatuvely Cooled Condenser”, Journal of Solar Energy Engineering, Vol. 115, pp.206-211,1993.
[9] Qureshi, B. A. Zubair, S. M., ”A comprehensive design and rating study of evaporative coolers and condensers”, International Journal of Refrigeration, Vol. 29, pp.645-668,2005.
[10] 林建志,「R410A應用於蒸發式冷卻空調系統性能分析與系統模擬之研究」,國立台北科技大學碩士論文,民97,第66-67頁。

被引用紀錄


郭議聯(2012)。間接蒸發式冷卻技術應用於VRF系統之節能分析與系統模擬〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-2606201213564500
翁明群(2013)。蒸發冷卻應用於氣冷式可變冷媒系統的性能研究〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-2406201313423000

延伸閱讀