透過您的圖書館登入
IP:3.137.192.3
  • 學位論文

澎湖離島風力發電佔比上限之研究

Study Of Wind Power Penetration Limitation In Penghu Island

指導教授 : 陳斌魁
若您是本文的作者,可授權文章由華藝線上圖書館中協助推廣。

摘要


台灣近年來大力推動風力發電等再生能源的發展,並將在澎湖等離島地區設置多部風力機組。然而由於風力發電輸出的不穩定性,當風力機出力佔比較高時,將對系統電壓、頻率和供電可靠度造成影響,進而影響澎湖電力系統之電網規劃以及運轉,故對於澎湖電力系統承受多少容量的風力發電,才不致造成系統安全運轉問題,是一項非常重要的議題。為此,本研究以IEC 61400-21規範評估風機併網之電力品質為依據,並依線路容量、電力品質、可靠度、運轉頻率限制及斷路器遮斷容量限制等五項評估準則,利用PSS/E電力系統模擬軟體,針對澎湖地區從民國96年至民國101年間,台澎海底電纜尚未興建之前,提出風機佔比允許上限之評估步驟,以不同時期的發電及負載運轉模式為基礎,藉系統指標饋線評估事故後之電壓、頻率與機組反應特性,來評估最大風力發電佔比。

關鍵字

風力發電 佔比

並列摘要


Taiwan lend an impetus to develop renewable energy in recent year, such as wind power generation, and TPC is planning to install a large amount of wind generators at offshore island Penghu. However it may affect power quality and reliability of Penghu Power System due to wind generation variability, and influence the planning and operation of Penghu power system with high wind penetration . How many wind generation penetration allowed is an important issue since the system security is highly concerned. This research based on IEC 61400-21 standard to determine the power quality when wind turbines connection to power system, based on transmission capacity, power quality , the limited frequency and the breaker capacity, focuses on the years range from 2007 to 2012 that before constructing the submarine cable connecting between Penghu island and Taiwan, simulates the power system contingencies based on generation and load operation pattern in different periods by adopting the power system simulation program PSS/E. This research considers the index feeder post fault power quality in distribution system by the voltage, frequency and generator response characteristic from system disturbance, and to determine the maximum allowed wind penetration in Penghu island.

並列關鍵字

wind power penetration

參考文獻


[1] Arthouros Zervos and Steve Sawyer, “Global Wind 2008 Report”, Global Wind Energy Council.
[9] S. Ž. Djokic´, J. Desmet, G. Vanalme, J. V.Milanovic´, and K. Stockman,” Sensitivity of Personal Computers to Voltage Sags and Short Interruptions,” IEEE Transactions on Power Delivery, Vol. 20, No. 1, JANUARY 2005.
[12] 陳唯泰,“考慮風力發電併入澎湖電力系統保護策略之研究”,大同大學碩士論文, July 2008。
[16] Beljaars, A.C.M. (1987) The Influence of Sampling and Filtering on Wind Gusts. Journal of Atmospheric and Oceanic Technology, 6, 613-626
[2]“日本甑島風力發電與柴油發電併聯運轉經驗報告”,台灣電力公司。

被引用紀錄


韓承澔(2015)。再生能源發電高滲透率之配電饋線分析-對再生能源發電系統併聯技術要點之檢討〔碩士論文,中原大學〕。華藝線上圖書館。https://doi.org/10.6840/cycu201500575
吳滄堯(2010)。澎湖獨立系統風力發電最大占比及系統穩定度分析〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-1907201017485900
姚君憲(2011)。使用DFIG與DDSG分別評估澎湖風力發電最大占比〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-2801201110341000

延伸閱讀