本研究以行政院環保署公告標準量測方法及直讀式儀器量測方法,進行辦公及寺廟建築室內空氣品質現場量測。研究結果發現,直讀式儀器針對室內CO、CO2、O3、PM10及PM2.5濃度進行量測所得讀值透過迴歸方程式修正後,可信度接近公告方法的量測結果。建築室內空氣品質最佳化量測方法應充分發揮直讀式儀器之優勢,即進行公告方法量測前,可於現場巡檢階段視建築物類型及現場條件,使用直讀式儀器進行室內空氣品質即時量測,以有效掌握不同類型建築室內空氣污染情形,落實建築室內空氣品質自主管理。
This study measured IAQ in office buildings and temples with two sets of methods, including standard methods of measurement and using direct-reading instruments. It was found that the concentrations of indoor CO, CO2, O3, PM10 and PM2.5 measured with direct-reading instruments were believable after adjusted by regression equation. It’s suggested that optimum methods for measurement of IAQ should take advantage of the direct-reading instruments depending on types of buildings and locale conditions for walk-through inspection to get information of IAQ effectively and practice IAQ self-management before measuring IAQ with standard methods of measurement.