具有自備電源系統之大型科技廠高壓與低壓系統開關突波特性及其影響研究

Switching Surge Characteristics of HV and LV Systems in the Large High-Tech Industrial Plants Considering the Backup Power Supply System

指導教授 : 周至如

摘要


本論文探討大型科技,廠內高壓及低壓供電系統之開關突波特性,其中考慮自備電源系統及市電系統,併聯運轉及獨立運轉之情形。文中首先以電磁暫態分析程式(ATP)建構電路模型(ATP模型),模型中涵蓋主變電站等效電源、低壓自備電源、高壓變壓器、避雷器、高低壓電纜線路、功因補償電容、諧波濾波器、高壓變電站地網、自備電源地網及下游地網等之參數。然後分析各種開關操作時之突波電壓及電流變化,其中開關操作程序將考慮正常操作及異常操作,而開關操作模式包括三相同步操作及三相非同步操作模式。操作類型含投入及切離兩種。經由ATP分析結果,可分別獲得供電系統及接地系統重要位置之開關突波電壓及電流。為進一步分析接地系統之電磁特性,本文再應用接地系統電磁分析軟體(CDEGS),以分析開關突波電流注入接地系統後之地電位昇、接觸電壓、步間電壓及地表電磁場分佈之概況。最後藉由上述分析結果評估其影響包括對於人員與設備之影響。本研究分析結果可供後續防範及保護措施之參考價值。

並列摘要


In this thesis, the switching surges characteristics of high-voltage (HV) and low voltage(LV) distribution systems in a high-tech industrial plant are studied considering both the utility supply source and backup power supply systems under parallel operation or individual operation. The model of the distribution system is first constructed based on the alternative transient program(ATP), in which the equivalent source systems of main substation, HV transformers, arresters, power cables, power factor correction capacitors, harmonic filters, HV substation grounding systems, backup power system grounding systems and down-stream grounding systems are all considered. Then, the surge voltages and currents of distribution system are analyzed by ATP simulations with respect to normal and abnormal switching procedures, synchronizing and non-synchronizing switching mode, and open and close operations. Furthermore, injected switching surge currents at various grounding points are obtained from simulation. The electromagnetic characteristics of grounding system are analyzed by a software package, namely “current distribution electromagnetic grounding and soil structures analysis” (CDEGS), to obtain the distribution of ground potential rise (GPR), touch voltage, step voltage and the electromagnetic fields (EMF) on the ground surface. Finally, the affections of switching surge characteristics of distribution system and grounding system are evaluated based on above analysis results. The study results of this thesis will contribute to plan and design the improved measures for previewing switching surge damages in a high-tech industrial plant.

參考文獻


[30]溫茂廷,特高壓地下環路接地系統開關突波特性研究,中原大學碩士論文,民國九十五年六月。
[26]黃鈺倫,捷運系統主變電站接地系統之開關突波特性分析,碩士論文,私立中原大學電機工程學系,中壢,民國九十一年六月。
[22]鍾政良,特高壓供電科技廠配電系統及接地系統之開關突波特性分析及其影響評估,國立台北科技大學碩士論文,民國九十七年六月。
[40]陳子立,超高壓變電所開關突波特性及其對接地系統之影響研究,碩士論文,私立中原大學電機研究所,中壢,民國九十六年六月。
[21]吳孟昌,大型高科技工廠接地系統雷擊與開關突波特性分析,碩士論文,私立中原大學電機研究所,中壢,民國九十一年六月。

被引用紀錄


范振航(2014)。二次變電所及饋線之雷擊及開關突波特性分析及其對低壓用戶之影響評估〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://doi.org/10.6841/NTUT.2014.00077

延伸閱讀