資料中心耗能監測與模擬分析–以某商業金融中心為例

Energy Monitoring and Simulation of Data Center — a Case Study of Commercial Bank

指導教授 : 李魁鵬

摘要


本研究以探討資料中心的系統規畫及耗能狀況,並選擇國內某一知名金融機構之大型企業級資料中心為樣本,進行各類設備及空調耗能的監測、各類設備的效率與特性解析、各設備設備用電比例,以及節能改善評估模擬分析。其量測結果顯示,總用電平均需量為 299.36 kW、EUI為4565 kWh/yr.、PUE為1.68、DCiE為0.59,並與其他建築之耗能指標相比較,本研究案例與美國資料中心平均PUE耗能指標1.63相近,因此本研究樣本具有可做為日後資料中心耗能研究之比較參考基準。 藉由監測所得之耗能資料,透過eQuest動態能源分析軟體進行全年度耗能模擬為2623.1 MWh,並針對此資料中心,在不變更資訊設備與空調系統配置,同時不危害運行安全性的條件下,研究可行的節能與節費措拖,如:冷卻水系統修正、UPS減載、照明時間控制,以及變更為三段式時間電費等。 上述各種措施進行全年度耗能與電費的計算與比較,其節能潛力為5.62 %,節省電費潛力為10.51%。

並列摘要


This research aims at the power monitor of equipment in a data center of banking organization. And the efficiency, characteristic, energy-use breakdown of each equipment, and energy saving potential are analyzed. The average power demand is 299.36 kW. Total annual energy consumption is 2623.1 MWh. The EUI of this data center is 4565 kWh/yr, PUE 1.68, and DCiE 0.59. The PUE of this case quite approaches to the PUE of 1.63 averaged from the survey data by LBNLUSA. Therefore this study case will be a good example for the future research. Without compromise of the normal operation of data center, the annual energy saving potential is estimated as 5.62%, and the saving cost 10.51% by the computer dynamic energy simulation program, eQUEST. The energy conservation measures include: correcting the operation of cooling water system, reducing the capacity of UPS system, lighting time control, and using the three stage time-of-use charge for saving cost.

參考文獻


[1] U.S. Environmental Protection Agency (EPA) - Engery Star Program, "Report to Congress on Server and Data Center Energy Efficiency-Public Law 109-431," 2007, pp.19-49.
[2] Pacific Gas and Electric Company, "High Performance Data Centers, A Design Guidelines Sourcebook," 2006, pp. 57.
[6] 陳相輪,非製造業能源大用戶建築耗能統計分析與診斷系統之研究,碩士論文,國立臺北科技大學能源與冷凍空調工程系研究所,台北,2007。
[3] Lawrence Berkeley National Laboratory and Rumsey Engineers, Inc., "Data Center Energy Benchmarking Case Study, Facility 8," 2003, pp. 2.
[4] Neil Rasmussen, "Electrical Efficiency Measurement for Data Centers," White Paper #154, 2008, pp. 3.

被引用紀錄


徐凡耘(2011)。R公司之高效率資訊中心建置與節能探討〔碩士論文,國立中央大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0031-1903201314414105
邱鈺欽(2011)。應用量測與驗證選項D之實例分析與其標準作業程序之建立〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-2706201115591400

延伸閱讀