透過您的圖書館登入
IP:18.224.37.68
  • 學位論文

三相四線式獨立型低壓微電網系統故障分析及保護協調最佳化研究

Fault Analysis and Optimal Protective Coordination for Three-Phase Four-Wire Stand-Alone Low Voltage Micro-Grid

指導教授 : 周至如

摘要


本文探討三相四線式獨立型低壓微電網供電系統之故障特性分析並以最佳化模式規劃其保護協調,其中考慮系統有多重分散式電源,故障特性包括三相短路故障、兩相短路故障及單相接地故障之特性。本文首先以電磁暫態分析軟體(EMTP/ATP)建構三相四線式獨立型低壓微電網供電系統模型(ATP模型),然後針對低壓微電網供電系統於不同故障點及不同故障類型下,進行分析各位置之電壓及電流變化。故障點涵蓋主匯流排、饋線與負載端,而故障類型包括三相短路故障、兩相短路故障及單相接地故障。根據故障特性之分析結果,本文進一步應用基因演算法規劃新型數位電驛之保護協調,電驛類型考慮過電流電驛及方向性過電流電驛為主。最後針對最佳規劃結果與傳統規劃結果進行比較,驗證本文所提之方法具可行性且為最佳解,可提供微電網適當保護協調並提昇微電網供電系統之保護。

並列摘要


In this thesis, the fault characteristics of the three-phase four-wire stand-alone low voltage micro-grid power supply system are analyzed, and the protection coordination is optimally planned in which the multiple distributed generating sources are taken into account. The fault characteristics include three-phase short circuit fault, two-phase short-circuit fault and single line ground fault characteristics. First of all, the system model is constructed based on alterative transient program of electromagnetic transients program (EMTP/ATP). Then, the voltages and currents of various fault points on the system during various faults are analyzed based on ATP model. The fault points include main bus, feeders, and load terminal, while the fault types include three-phase short-circuit fault, two-phase short-circuit fault and single-phase to ground fault. Based on the fault analysis results, the protection coordination of system is planned according to genetic algorithm (GA) and novel digital relays which include directional overcurrent relays and overcurrent relays. Finally the results of protective coordination planning by GA are compared with the results obtained from conventional planning method to verify the feasibility proposed method, and to show that the proposed method can provide adequate protection for micro-grid coordinate and enhance the protection of the micro-grid power supply system.

參考文獻


[1] 陳彥豪,陳彥宏,胡桓祥,「各國微電網示範計畫介紹」,台灣經濟研究月刊,第三十三卷,第七期,2010,第103-112頁。
[20] 陳彥宏,陳彥豪,左峻德,胡明哲,「微電網技術經濟性分析研究」,台灣經濟研究月刊,第三十三卷,第十一期,2010,第71-78頁。
[31] 鍾彰榮,過電流與測距電驛於輸電網路保護協調之研究,博士論文,國立臺北科技大學電機工程所,臺北,2009。
[32] 莊家祥,低壓微電網供電系統故障特性分析及保護協調研究,碩士論文,國立臺北科技大學電機工程系碩士班,臺北,2011。
[2] A Alberto J. Urdaneta, Ramon Nadira Luis and GPdrez Jimdnez, “Optimal Coordination of Directional Overcurrent Relays in Interconnected Power System,” IEEE Transactions on Power Delivery, Vol. 3, July 1988, pp. 903-911.

被引用紀錄


林恆安(2014)。大型離岸風場長距離海底電纜之測距電驛保護區域規劃〔碩士論文,國立臺北科技大學〕。華藝線上圖書館。https://www.airitilibrary.com/Article/Detail?DocID=U0006-1407201412192700

延伸閱讀